PipeForge Vicv1 Victaulic Grooved Take-Off
System Original Groove System
⚠
Field reference tool only. Always verify dimensions against current Victaulic literature before fabrication. Sources: 07.01, 25.01, 25.09, 51.01, I-100.

Grooved Take-Off Calculator

OGS

How This Works

Method

Victaulic grooved systems are not threaded. There is no thread makeup to add or subtract. Cut length is calculated using each fitting's published center-to-end (CTE) dimension straight off the catalog:

Cut = Field − (CTE_A + CTE_B)

A coupling between two bare pipe ends adds essentially zero length — the gasket bridges the pipe-end gap, and CTE for a "bare end into coupling" is treated as 0. Use C–E or E–E modes for those situations.

Roll grooving deforms the pipe wall and removes no metal. Cut grooving removes material. Both methods produce the same C dimension when done to spec — see Inspection tab.

Multi-Segment Run

Chain
Add segments for a continuous run. Each segment has its own field measurement, mode, and end fittings.

Fitting CTE Lookup

OGS
Source: Victaulic Publication 07.01 — Verify Rev against current submittal.
SizeCTEThrowWeightNotes

Groove Dimensions

OGS
A = gasket seat  ·  B = groove width  ·  C = groove diameter PASS/FAIL  ·  D = groove depth (reference only)  ·  F = max flare diameter  ·  T = min wall thickness
Source: Victaulic 25.01 (OGS). Groove diameter C is the inspection acceptance dimension.
Pipe Size OD A (Gasket Seat) B (Groove Width) C (Groove Dia) ★ D (Depth Ref) F Max Flare T Min Wall

Groove Inspection

OGS
★
Groove diameter C is the acceptance dimension. Depth D is reference only — a groove can be at correct depth but out-of-spec on C if the pipe OD is off, and vice-versa. Always verify with a Victaulic verification gauge or pi tape.

Quick Reference Cards

Field Ready

Victaulic Literature

Official
All dimensions in this app derive from these official Victaulic publications. Tap any card to open the PDF in your browser. Always check for the most current revision before fabrication.